EN 50288-7/BS 5308 Part 1 Fire Resistant MICA/XLPE/ICAM/LSZH Instrumentation Cable

Voltage:300/500V
Conductor: flexible or stranded Copper
Insulation: MICA Tape + XLPE (Cross-Linked Polyethylene)
Individual and Collective Screen: AL/PET+Drain Wire
Sheath: LSZH (Low Smoke Zero Halogen)
Main Application: designed to connect electrical instruments and communication systems in process plants such as petrochemical industry.

EMAIL

EN 50288-7/BS 5308 Part 1 Fire Resistant MICA/XLPE/ICAM/LSZH Instrumentation Cable

Application

When you are managing the process plants such as petrochemical plants or other process facilities, you can use these instrumentation cables to deliver the reliability you require to keep your instrument circuits and communication services running smoothly. You should install these cables in cable trays or ducts, as they are not designed for direct burial.

If you need specification beyond our standard range, please contact with us by email , tailored quotation will be in your inbox!

Structure

Conductor 

0.5mm² - 0.75mm²: Class 5 flexible Copper

1mm² and above:    Class 2 stranded Copper

Insulation

MICA Tape + XLPE (Cross-Linked Polyethylene)

Individual and Collective Screen

Al/PET (Aluminium/Polyester Tape) + tinned copper

Sheath 

LSZH (Low Smoke Zero Halogen)

Color

Can be customized

Technical data

Voltage

300/500V

Operating Temperature: 

Fixed: -40°C to +80°C 

Flexed: 0°C to +50°C

Minimum Bending Radius 

6 x overall diameter

Standards

EN 50288-7/EN 50288-1/EN 60228/BS 5308

Flame Retardant refer to IEC/EN 60332-1-2, IEC/EN 60332-3-24

Certificates

We have certificates such as KEMA/CE/TUV/UL/GOST/EAC/RoHS/CNAS under international standards